B2AB149

This DTC indicates a phase loss in the internal three-phase permanent magnet synchronous motor of the electric A/C compressor (E-Compressor) — Seal 6 EV

Thermal Management System

This DTC indicates a phase loss in the internal three-phase permanent magnet synchronous motor of the electric A/C compressor (E-Compressor).

When the compressor controller (inverter) supplies power to the motor U/V/W three-phase windings, it detects a loss of at least one phase current or a voltage drop exceeding the threshold.

Open windings, open high-voltage harnesses, or damaged IGBT power modules typically cause this condition.

This fault prevents the compressor from generating effective torque and forces it to stop, which disables the A/C cooling and heating functions and triggers the thermal management system derating protection.

In vehicles like the BYD Qin EV, battery cooling relies on the A/C refrigerant circuit; therefore, this fault may indirectly raise the battery pack temperature and limit charge and discharge power.

4
Cases Logged
5
Causes
  • 1Compressor high-voltage wiring harness connector burnt or loose: Long-term vibration or excessive contact resistance overheats the three-phase high-voltage plug (usually located on top of the compressor). This causes pin ablation or recession, resulting in an open circuit in one phase.
  • 2Electric compressor controller (IPM module) fault: Breakdown of the upper or lower bridge arms for one or more phases in the built-in IGBT power module, or a damaged drive circuit, preventing the output of a complete three-phase sine wave voltage.
  • 3Compressor motor winding burnt out: Insulation breakdown, overheating, or overload causes an open circuit (infinite resistance) or inter-turn short circuit in one phase of the internal three-phase winding.
  • 4High-voltage distribution box compressor fuse blown or relay stuck: One phase of the 500V/20A fast-acting fuse blows in the high-voltage power supply circuit, or burnt high-voltage contactor contacts cause an unbalanced three-phase power supply.
  • 5Low-voltage control signal fault: CAN communication fault between the thermal management system (TMS) controller and the compressor controller, or abnormal 12V control power supply/enable signal causing the controller to falsely detect a phase loss.
  • 1
    Diagnostic scan: Use VDS2000/3000 to read all fault codes. Check for accompanying B2AB2-49 (IPM fault), B2AB3-11 (compressor overcurrent), or high-voltage interlock faults. Record freeze frame data at the time of the fault (bus voltage, three-phase current values).
  • 2
    High-voltage safety check: Disconnect the low-voltage battery negative terminal, wait 5 minutes, put on insulated gloves, remove the compressor high-voltage service disconnect, and verify the high-voltage system has no residual voltage (<60V DC).
  • 3
    High-voltage wiring harness inspection: Check the compressor three-phase high-voltage connector (orange-yellow) for burning, terminal back-out, or water ingress. Use a multimeter to measure the continuity of the three-phase wiring harness at the connector end (U-V, V-W, W-U); normal resistance is <1Ω. Use a 1000V megohmmeter to measure the insulation resistance from the three phases to the housing; resistance must be >500MΩ.
  • 4
    Motor winding inspection: Disconnect the compressor high-voltage connector and directly measure the three-phase DC resistance at the compressor terminals (U-V, V-W, W-U). Normal values are 0.5-2.0Ω with a three-phase imbalance rate <5%. If any phase reads infinite resistance, the motor winding has an open circuit; replace the compressor assembly.
  • 5
    Controller function check: Restore the low-voltage power supply and use the diagnostic tool to perform the compressor Active Test. Use an oscilloscope to measure the three-phase voltage waveforms at the controller output terminals. The oscilloscope must display symmetrical three-phase sine waves. If any phase lacks a waveform output, the controller is faulty. Replace the compressor controller or the entire compressor assembly (BYD typically supplies the complete assembly).
  • 6
    System reset verification: After repair, clear the fault code. Vacuum-fill the thermal management system and charge the refrigerant. Perform a 30-minute air conditioning operation test. Monitor the three-phase current balance (current difference between phases <10%) and confirm the fault code does not recur.
BYD DTC AI Analysis

Burnt high-voltage plug on Qin EV compressor causing intermittent phase loss

Intermittent AC cooling failure. Read DTC B2AB149. Inspection found visible burning and blackening on U-phase terminal of compressor high-voltage connector. Measured U-phase contact resistance at 12Ω (normal <0.1Ω). Poor contact caused arcing under high current, gradually burning the terminal. Replaced compressor high-voltage wiring harness assembly (including connector) and applied conductive paste. Issue resolved.
BYD DTC AI Analysis

Damaged electric compressor IGBT module triggered phase loss protection

Total AC failure with DTCs B2AB149 and B2AB2-49. Removed and inspected the compressor controller; found the V-phase lower bridge arm IGBT in the IPM module shorted. Compressor windings measured normal. Isolated to controller power device quality defect. BYD does not offer standalone controller repair, so replaced the electric compressor assembly. System restored to normal with balanced three-phase current.
BYD DTC AI Analysis

Refrigerant leak caused compressor overheating and phase loss

Owner reported AC cooling gradually weakened until complete failure. DTC B2AB149 stored. Found severe refrigerant leak (pressure <0.1MPa). Compressor ran dry for an extended period without oil or refrigerant, overheating the motor windings and damaging insulation until the V-phase winding opened. Replaced compressor, repaired condenser leak, and charged standard refrigerant (450g R410a) and refrigeration oil. Fault resolved.
BYD DTC AI Analysis

High-voltage distribution box relay contacts burned

AC cut in and out. DTC B2AB149 intermittent. Compressor relay contacts inside HV distribution box severely burned, causing W-phase power to drop out. Relay coil tested normal, but contact resistance fluctuated with vibration. Replaced distribution box relay (or complete assembly). Fault code cleared and did not return; three-phase voltage balanced and stable.
Data confidence: Official This information is for reference only. Always consult a qualified technician for diagnosis and repair. Do not attempt high-voltage system repairs yourself.