This DTC indicates abnormal three-phase inverter voltage in the electric A/C compressor (electric scroll compressor) drive system — Seal 6 EV
This DTC indicates abnormal three-phase inverter voltage in the electric A/C compressor (electric scroll compressor) drive system.
Specifically, the Intelligent Power Module (IPM) driving the compressor's built-in Permanent Magnet Synchronous Motor (PMSM) detects the equivalent voltage of any U/V/W phase exceeding the safety threshold (typically >650V DC peak voltage after PWM modulation).
This fault triggers a protective compressor shutdown, disabling the A/C system.
It may also derate the vehicle thermal management system, affecting power battery cooling and heating functions.
Fundamentally, this indicates a high-voltage drive circuit or voltage sampling circuit fault.
Determine whether the condition is a true overvoltage (high-voltage bus fault) or a false overvoltage (sensor drift).
- 1Abnormal bus voltage surge in the high-voltage power distribution system, such as: overvoltage output from a DC fast charger, abnormal regenerative braking energy recovery causing instantaneous power battery overcharge, or a faulty precharge/voltage divider resistor in the high-voltage power distribution box causing sampled voltage distortion.
- 2Compressor controller (IPM module) voltage sampling circuit fault: Voltage divider resistor drift, operational amplifier damage, or ADC chip failure causes the controller to falsely detect excessively high phase voltage.
- 3Compressor three-phase high-voltage wiring harness insulation damage: Harness wear causes high voltage to leak into the low-voltage signal circuit, or shielding failure introduces electromagnetic interference, causing voltage sampling values to spike.
- 4Compressor motor insulation deterioration: Insulation resistance between the motor winding and housing drops (<20MΩ), generating abnormal back EMF or leakage current that the controller misinterprets as overvoltage.
- 5Software calibration or control strategy fault: Communication delay between BMS and A/C controller causes an abnormal voltage command, or overvoltage threshold (OVP) calibration in compressor drive software is too sensitive.
- 1Read freeze frame data: Use the BYD VDS2000/3000 diagnostic tool to read the freeze frame at the time of the fault. Record the high-voltage bus voltage (HV Voltage), phase current (Phase Current), compressor speed (RPM), and IGBT temperature to determine if the condition is a steady-state overvoltage or a transient spike.
- 2High-voltage system voltage verification: In Ready mode, use a CAT III 1000V multimeter to measure the total traction battery voltage. Compare this value with the diagnostic tool reading. The deviation must be <5V. Check the fast-charging port CC/CP signals and BMS data stream to rule out charging system overvoltage.
- 3Compressor insulation resistance test: Disconnect the compressor high-voltage manual service disconnect (MSD). Wait 5 minutes for the capacitors to discharge. Use a 1000V megohmmeter to measure the insulation resistance between the three-phase lines (U/V/W) and the compressor housing. Standard value: >500MΩ (Qin EV). If the resistance is <20MΩ, replace the compressor.
- 4Low-voltage signal circuit check: Check the 5V reference voltage (Vcc), voltage sampling signal (Vout), and ground (GND) pins at the compressor controller low-voltage connector (usually 12-pin). Normal value: 5V ± 0.25V. Verify the wiring harness shield ground is secure.
- 5Swap verification test: Swap the electric compressor assembly (or only the compressor controller, if detachable) with one from the same model. Run the air conditioning at full load for 30 minutes. Observe if the fault transfers to isolate the faulty component.
- 6Software update and matching: If hardware is normal, update the Air Conditioning Controller (ACU) and Battery Management System (BMS) software to the latest version. Perform compressor initialization matching (some models require 'compressor phase learning').
- 7System reset and verification: Clear the fault code, perform high- and low-voltage charge and discharge tests (fast charging + high-power cooling), and continuously monitor the phase voltage data stream. Release the vehicle after confirming no abnormalities.
Qin EV Air Conditioning Failure After Fast Charging
Compressor controller sampling circuit fault
Three-phase harness insulation failure from wear.
Improper software calibration caused false positive
Compressor motor winding insulation deterioration