This fault code indicates the internal drive current of the thermal management system electric scroll compressor (E-Compressor) exceeds the safety threshold set by the MCU (microcontroller unit) (typically peak current >45A or sustained RMS current >15A) — Seal U
This fault code indicates the internal drive current of the thermal management system electric scroll compressor (E-Compressor) exceeds the safety threshold set by the MCU (microcontroller unit) (typically peak current >45A or sustained RMS current >15A).
This hardware-level protection fault indicates the compressor permanent magnet synchronous motor (PMSM) or its integrated controller (including the IPM intelligent power module) detects abnormal current consumption.
During compressor start-up or operation, the controller triggers this fault if Hall sensors detect a three-phase current imbalance exceeding 10%, or if the instantaneous DC bus current exceeds the calibrated limit (approximately 22-25A) for over 100ms.
The compressor stops immediately to protect the IGBT power devices, affecting cabin air conditioning cooling/heating and battery pack liquid cooling functions.
A prolonged fault may burn out the compressor controller or blow the high-voltage fuse (typically 30A-40A).
- 1Inter-turn short circuit or reduced phase-to-phase insulation (insulation resistance <20MΩ) in the electric compressor internal motor winding, causing an abnormal increase in electromagnetic load and a surge in operating current.
- 2Compressor integrated controller fault, including IGBT breakdown in the IPM (Intelligent Power Module), current sampling resistor (shunt resistor) drift, or gate drive circuit malfunction causing three-phase drive waveform distortion.
- 3Excessive mechanical load on the air conditioning system, such as refrigerant overcharge (exceeding the standard value of 550g±25g), blocked receiver-drier/expansion valve causing excessive high-side pressure (>2.5MPa), internal compressor mechanical seizure, or lack of compressor oil (POE oil) causing poor lubrication.
- 4Abnormal high-voltage power supply circuit, including a burnt battery pack contactor causing a voltage drop (<320VDC), increased high-voltage wiring harness contact resistance (>10mΩ) causing voltage fluctuations, or EMC interference distorting the current sampling signal.
- 5Thermal management control strategy or software calibration defects, such as start-up current ramp control failure, abnormal closed-loop speed PID parameters causing current surges, or refrigerant migration causing liquid slugging during sudden ambient temperature drops.
- 1Use the VDS2000/3000 diagnostic tool to read the complete fault codes and freeze frame data. Record the following key parameters at the time of the fault: compressor speed (rpm), high-voltage bus voltage (V), three-phase current values (A), refrigerant high- and low-side pressures (kPa), IGBT temperature (℃), and fault occurrence count (Trip Counter).
- 2Perform the standard high-voltage power-down procedure (turn off the ignition switch, disconnect the low-voltage battery negative terminal, and wait 5 minutes). Wear CAT III 1000V insulated gloves. Use an insulation resistance tester to measure the insulation resistance between the compressor high-voltage input terminal and the vehicle body (standard: >500MΩ).
- 3Check the air conditioning system static pressure (0.9-1.1 MPa at 25°C ambient temperature). Use a manifold gauge to check the dynamic pressures on the high and low sides (normal low pressure: 0.15-0.25 MPa; high pressure: 1.3-1.6 MPa). Confirm there is no ice blockage, debris blockage, or excessive refrigerant. Check the sight glass to confirm the refrigerant oil color and foam condition.
- 4Disconnect the compressor low-voltage connector (usually 8-pin or 12-pin). Measure the DC resistance of the three-phase windings (U-V-W) using a micro-ohmmeter (standard value: 0.8-1.5Ω at 20°C) and calculate the three-phase imbalance (must be <5%). Measure the insulation resistance of each phase to the housing using a megohmmeter (must be >20MΩ).
- 5Check the high-voltage interlock loop (HVIL) for continuity, measure the voltage drop across the high-voltage contactor contacts (should be <0.1V), verify proper grounding of the compressor high-voltage wiring harness shield, and confirm the supply voltage is within the 320-420VDC range with no severe fluctuations (ripple <5%).
- 6If winding resistance is abnormal or insulation fails, replace the electric compressor assembly (part number may be BC-8103020E or similar). For refrigerant issues, recover the refrigerant using a recovery machine, replace the desiccant, evacuate the system to -0.1 MPa, and hold pressure for 15 minutes. Recharge with the standard amount (450-550 g, depending on the specific model) of R134a or R1234yf and the corresponding compressor oil (approx. 120-150 ml).
- 7After replacement, perform the compressor self-learning procedure (if applicable). Use the diagnostic tool to run an active test to verify the compressor operates normally across the full speed range (1000-6000rpm), the current stabilizes within 3-12A, and there is no abnormal noise. Perform a 30-minute road test to verify the thermal management function and confirm the fault code does not return.
Qin EV compressor winding insulation degradation causes intermittent overcurrent
Ice blockage in refrigerant system triggered compressor overload protection
Burned high voltage contactor caused abnormal compressor current.
Drift in the compressor controller sampling resistor caused false fault reports.